cal1-80-rccb-2p
cal1-80-rccb-2p
cal1-80-rccb-4p

CAL1-80 6kA RCCB

CAL1-80 Series RCCB is the latest products developed by Changan Electric,In max 80A.The product has a novel appearance and adopts a plastic operating mechanism, which is more stable and environmentally friendly, with lower cost and competitive price.

feedback
Product Description

CAL1-80 Series RCCB is the latest products developed by Changan Electric,In max 80A.The product has a novel appearance and adopts a plastic operating mechanism, which is more stable and environmentally friendly, with lower cost and competitive price.

Electrical Features

 

Mode

Electromagnetic

Type

AC,A,G,S

Rated current In

25,40,63,80A

Poles

2P(1P+N)/4P(3P+N)

Rated voltage Ue

2P 230/240V~

4P 400/415V~

Insulation voltage Ui

500V

Rated frequency

50/60Hz

Rated residual operation current(I△n)

30,100,300mA

Rated residual making and breaking capacity(I△m)

500A(In≤40A),10In(In>40A)

Short-circuit current Inc=I△c

6,000A

SCPD fuse

6000

Break time under I△n

≤0.1s

Rated impulse withstand voltage(1.5/50) Uimp

4000V

Dielectric test voltage at ind.Freq. for 1min

2.5kV

Electrical life

2,000Cycles

Mechanical life

4,000Cycles

Installation

 

Contact position indicator

Yes

Protection degree

IP20

Ambient temperature(with daily average≤35℃)

-5℃~+40℃

Storage temperature

-25℃~+70℃

Terminal connection type

Cable/Pin-type busbar

Terminal size top/bottom for cable

35mm2 18-2AWG

Terminal size top/bottom for busbar

35mm2 18-2AWG

Tightening torque

2.5Nm 22In-lbs

Mounting

On DIN rail EN60715(35mm) by means of fast clip device

Connection

Power supply in both directions

Tripping Current Range

Type

Tripping current I△/A

AC

0.5I△n<I△<I△n

A

Lagging Angle

I△n>0.01A

I△n≤0.01A

0.35I△n≤I△≤1.4I△n

0.35I△n≤I△≤2I△n

90°

0.25I△n≤I△≤2I△n

0.25I△n≤I△≤2I△n

135°

0.11I△n≤I△≤1.4I△n

0.11I△n≤I△≤2I△n

Characteristics Curves

Alternative Current Sensitive Pulsating direct current sensitive Surge current proof

They react to AC current which, whether suddenly applied or slowly arising.

They react to AC and pulsating DC fault current which reach 0 or almost 0 within one time period of the mains frequency. RCCB’s surge capacity.
Not tripping at standardized 8/20 υs surge-current waves acc.to VDE 0432 Part 2 with surge current values of up to 250A.

Circuit Diagram

Overall and Installation Dimension(mm)

 

Feedback