EKL1-63B 10kA Electromagnetic Type B RCCB
EKL1-63B 10kA Electromagnetic Type B RCCB

EKL1-63B 10kA Electromagnetic Type B RCCB

feedback
Product Description

EKL1-63B Type B RCD has novel appearance design, compact structure, good reliability, and high safety. The products comply with IEC61008-1, IEC62423 and other standards, and the product certification is complete; They ensure higher protection levels with maximum operational continuity under all working conditions. For this reason, Type B RCDs are considered universal devices because they provide protection against all the tripping waveforms listed in the Standards EN 62423.Type B RCDs can ensure maximum safety in many applications, such as EV Charging Station, Crane and Elevator, PV and Wind power plants, etc.

RCCB Electrical Features Mode Electromagnetic
Type (wave form of the earth leakage sensed) B
Rated current In 25,40,63A
Poles 2P(1P+N),4P(3P+N)
Rated voltage Ue 2P 240V~,4P 415V~
Insulation voltage Ui 500V
Rated frequency 50/60Hz
Rated residual operation current(I△n) 30mA
Rated residual making and breaking capacity (I△m) 500A(In≤40A), 10In (In>40A)
Short-circuit current Inc= I△c 10,000A
SCPD fuse
Break time under I△n ≤0.1s
Rated impulse withstands voltage (1.5/50) Uimp 4000V
Dielectric test voltage at ind. Freq. for 1min 2.5kV
Electrical life 2,000 Cycles
Mechanical life 4,000 Cycles
RCCB Installation Contact position indicator Yes
Protection degree IP20
Ambient temperature (with daily average≤35℃) -5℃~+40℃
Storage temperature -25℃~+70℃
Terminal connection type Cable/Pin-type busbar/U-type busbar
Terminal size top/bottom for cable 25mm2 18-3AWG
Terminal size top/bottom for busbar 25mm2 18-3AWG
Tightening torque 2.5Nm 22In-lbs
Mounting On DIN rail EN60715(35mm) by means of fast clip device
Connection Power supply in both directions
Tripping Current Range Lagging Angle I△n>0.01A I△n≤0.01A
0.35I△n≤I△≤1.4I△n 0.35I△n≤I△≤2I△n
90° 0.25I△n≤I△≤1.4I△n 0.25I△n≤I△≤2I△n
135° 0.11I△n≤I△≤1.4I△n 0.11I△n≤I△≤2I△n

 

Detectable wave form Pulsating direct current sensitive Surge current proof
B class
Tripping is ensured for sinusoidal AC residual currents pulsed DC residual currents, alternating residual sinusoidal currents up to 1000Hz, pulsating direct residual currents and for smooth direct residual currents, whether applied suddenly or increasing slowly.

They react to AC and pulsating DC fault currents which reach 0 or almost 0 within one time period of the main frequency.

RCCB’s surge capacity.
Not tripping at standardized 8/20 υs surge-current waves acc.to VDE 0432 Part 2 with surge current values of up to 250A.
Circuit Diagram

 